UKOOA TYPE PB 6.35/11kV Flame Retardant

Application

These cables are designed for use in fixed wiring on ships and offshore platforms and drilling rigs, especially used where life may be endangered by smoke and noxious fumes, and where sensitive equipment may be damaged by acid forming gases.

Standards

  • BS 6883/BS 7917/UKOOA
  • IEC 60332-3-22 CAT. A
  • IEC 60332-1
  • IEC 60754-1 & IEC 60754-2
  • IEC 61034-1 & IEC 61034-2

Construction

Conductors Stranded class 2 tinned annealed copper conductors to BS 6360/IEC 60228.
Conductor Screen Semi-conductive tape or an extruded layer of semi-conductive compound
Insulation EPR complying with BS7655 GP4
Insulation Screen Semi-conductive tape or an extruded layer of semi-conductive compound
Metallic Screen Copper Tape
Bedding CSP – SW2 or EVA - SW4 compound complying with BS 7655.
Armour Galvanised steel wire braid to BS 6883
Outer Sheath CSP – SW2 or EVA - SW4 compound complying with BS 7655.

Dimensions and Weight

Construction
No. of cores×Cross section(mm^2)
Nominal Insulation Thickness
mm
Nominal Thickness of Inner Sheath
mm
Nominal Thickness of Outer Sheath
mm
Nominal Overall Diameter
mm
Approx. Weight
kg/km
3×16 3.4 1.9 2.1 41.3 2660
3×25 3.4 2.0 2.3 45.1 3310
3×35 3.4 2.1 2.4 47.3 3960
3×50 3.4 2.2 2.5 50.2 4570
3×70 3.4 2.4 2.7 54.8 5610
3×95 3.4 2.5 2.8 61.0 6820
3×120 3.4 2.7 3.0 63.2 8070
3×150 3.4 2.8 3.1 66.6 9260
3×185 3.4 3.0 3.3 71.2 10060
3×240 3.4 3.2 3.6 81.1 13390
3×300 3.4 3.4 3.8 87.3 15730